Commissioning (Basic Settings); Open Switch Compartment; Torque Switching: Set - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Commissioning (basic settings)

10.
Commissioning (basic settings)
10.1.

Open switch compartment

10.2.

Torque switching: set

Information
44
The switch compartment must be opened to perform the following settings.
Ignition of potentially explosive atmospheres caused by sparks.
Risk of death or serious injury.
Before opening the flameproof enclosure, ensure absence of gas and voltage.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
1.
Loosen screws [2] and remove cover [1] from the switch compartment.
2.
If indicator disc [3] is available:
Remove indicator disc [3] using a spanner (as lever).
Information: To avoid damage to paint finish, use spanner in combination with
soft object, e.g. fabric.
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
SAEx 07.2
SAEx 16.2 / SAREx 07.2
SAREx 16.2