Terminal Compartment: Close - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Electrical connection
6.3.3.

Terminal compartment: close

Procedure
30
Figure 25: Close terminal compartment
[1]
Cover (illustration shows KT version in type of protection Ex e)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plug
[5]
Cable gland (example)
[6]
Connection frame (KT-Ex e)
1.
Clean sealing faces of cover [1] and connection frame [6].
2.
For design in flameproof enclosure (Ex d): Preserve joint surfaces with an acid-
free corrosion protection agent.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.
Fit cover [1] and fasten screws [2] evenly crosswise.
For design in flameproof enclosure (Ex d):
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
6.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
SAEx 07.2
SAEx 16.2 / SAREx 07.2
SAREx 16.2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Saex 16.2Sarex 07.2Sarex 16.2

Table of Contents