First Time Power-Up and Start-Up
Step
Action/Result
- If necessary, change the
value of P0296 according
to the line rated voltage.
To do so, press "Select".
This modification will
10
affect P0151, P0153,
P0185, P0321, P0322,
P0323, and P0400.
- If necessary, change the
value of P0298 according
to the inverter application.
To do so, press "Select".
This modification will
affect P0156, P0157,
P0158, P0401, P0404
11
and P0410 (this last one
only if P0202=0, 1, or
2 – V/f control). The time
and the activation level of
the overload protection
will be affected as well.
- If necessary, change the
value of P0398 according
to the motor service factor.
To do so, press "Select".
This modification will
12
affect the current value
and the activation time
of the motor overload
function.
- If necessary, change
5
the value of P0400
according to the motor
rated voltage. To do
so, press "Select". This
13
modification adjusts the
output voltage by a factor
x = P0400/P0296.
- If necessary, change the
value of P0401 according
to the motor rated current.
To do so, press "Select".
14
This modification will
affect P0156, P0157,
P0158, and P0410.
5-4
Display indication
Config
0rpm
LOC
Type of Control
P0202: V/F 60 HZ
Line Rated Voltage
P0296: 440 - 460 V
Reset
13:48
Select
Config
LOC
0rpm
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Heavy Duty
Reset
13:48
Select
Config
0rpm
LOC
Application
P0298: Heavy Duty
Motor Service Factor
P0398:
1.15
Reset
13:48
Select
Config
0rpm
LOC
Motor Service Factor
P0398:
1.15
Motor Rated Voltage
P0400:
440 V
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Voltage
P0400:
440V
Motor Rated Current
P0401:
13.5 A
Reset
13:48
Select
Figure 5.2 (cont.) - Oriented Start-up
Step
Action/Result
- If necessary, set P0402
according to the motor
rated speed. To do so,
press "Select". This
modification affects
15
P0122 to P0131, P0133,
P0134, P0135, P0182,
P0208, P0288, and
P0289.
- If necessary, set P0403
according to the motor
rated frequency. To do
so, press "Select". This
16
modification affects
P0402.
- If necessary, change the
value of P0404 according
to the motor rated power.
To do so, press "Select".
17
This modification affects
P0410.
- This parameter will only
be visible if the encoder
board ENC1 is installed in
the inverter.
- If there is an encoder
connected to the motor,
18
set P0405 according
to the encoder pulses
number. To do so, press
"Select".
- If necessary, set P0406
according to the motor
ventilation. To do so, press
"Select".
19
- To complete the
Oriented Start-Up routine,
press "Reset" (left soft
key) or
.
- After few seconds, the
20
display returns to the
Monitoring Mode.
Display indication
Config
0rpm
LOC
Motor Rated Current
P0401:
13.5 A
Motor Rated Speed
P0402:
1750 rpm
Reset
13:48
Select
Config
LOC
0rpm
Motor Rated Speed
P0402:
1750 rpm
Motor Rated Frequency
P0403: 60 Hz
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Frequency
P0403: 60 Hz
Motor Rated Power
P0404: 4hp 3kW
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Power
P0404:
4hp
3kW
Encoder Pulses Number
P0405:
1024 ppr
Reset
13:48
Select
Config
0rpm
LOC
Encoder Pulses Number
P0405:
1024 ppr
Motor Ventilation
P0406: Self-Vent.
Reset
13:48
Select
Ready
0rpm
LOC
0
rpm
0.0
A
0.0
Hz
13:48
Menu

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents