Installation and Connection
Control connection # 4 - Forward/Reverse.
Enabling the Forward/Reverse function.
Parameters to set:
Set DI3 to Forward run
P0265=4
Set DI4 to Reverse run
P0266=5
When the Forward/Reverse function is set, it will be active either in Local or Remote mode. At the same time,
the HMI keys
The direction of rotation is determined by the Forward run and Reverse run inputs.
Clockwise direction for Forward run and counterclockwise for Reverse run.
The speed reference can be provided by any source (as in the control connection # 3).
3
3-26
and
will remain always inactive (even if P0224=0 or P0227=0).
Stop/Forward S1
Stop/Reverse S2
Figure 3.19 - XC1 wiring for control connection # 4
XC1 Terminal Strip
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND *
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
DO1
22
C1
(RL1)
23
NO1
24
NC2
DO2
25
C2
(RL2)
26
NO2
27
NC3
DO3
28
C3
(RL3)
29
NO3