Conducted
emission -
Inverter model
maximum motor
cable length
Category C3
CFW110242T4
100 m
CFW11 0312T4
100 m
CFW110370T4
100 m
CFW110477T4
100 m
CFW110515T4
100 m
CFW110601T4
100 m
CFW110720T4
100 m
Notes:
(1) Information valid for networks with solid grounded neutral.
(2) With a toroidal core on the three mains cable (the three cables connected to R/L1, S/L2 and T/L3 must pass through a single toroidal core).
Example: TDK PN: PC40 UU120x160x20. If the inverter is installed inside a metallic cabinet with an attenuation of 10dB in the frequency range
[30; 50]MHz, that toroidal core is not required.
(3) 2.4 Hz minimum operating frequency.
Table 3.8 - Conducted and radiated emission levels
Without external RFI filter
Radiated emission
Category
C3
(2)
C3
(2)
C3
(2)
C3
(2)
C3
(2)
C3
(2)
C3
(2)
Installation and Connection
With external RFI filter
Conducted
External RFI
emission -
filter part number -
maximum motor
(manufacturer:
cable length
Epcos)
Category C2
B84143-B0250-S021
100 m
B84143-B0320-S021
100 m
B84143-B0400-S021
100 m
B84143-B0600-S021
100 m
B84143-B0600-S021
100 m
B84143-B0600-S021
100 m
B84143-B1000-S021
100 m
Radiated emission
Category
C3
(3)
C3
(3)
C3
(3)
C3
(3)
C3
(3)
C3
(3)
C3
(3)