Emission And Immunity Levels - WEG CFW-11 Series User Manual

Hide thumbs Also See for CFW-11 Series:
Table of Contents

Advertisement

Installation and Connection
Category C2: inverters with a voltage rating less than 1000 V intended for use in the First Environment,
not provided with a plug connector or movable installations. They must be installed and commissioned by a
professional.
Note: A professional is a person or organization familiar with the installation and/or commissioning of inverters,
including their EMC aspects.
Category C3: inverters with a voltage rating less than 1000 V and intended for use in the Second Environment
only (not designed for use in the First Environment).
Category C4: inverters with a voltage rating equal to or greater than 1000 V, or with a current rating equal to
or greater than 400 Amps, or intended for use in complex systems in the Second Environment.
EN 55011: "Threshold values and measuring methods for radio interference from industrial, scientific
and medical (ISM) high-frequency equipment"
Class B: equipment intended for use in the low voltage power supply network (residential, commercial, and
light industrial environments).
3
Class A1: equipment intended for use in the low voltage power supply network. Restricted distribution.
Note: It must be installed and commissioned by a professional when applied in the low voltage power supply
network.
Class A2: equipment intended for use in industrial environments.

3.3.3 Emission and Immunity Levels

EMC Phenomenon
Emission:
Mains Terminal Disturbance Voltage
Frequency Range: 150 kHz to 30 MHz)
Electromagnetic Radiation Disturbance
Frequency Range: 30 MHz to 1000 MHz)
Immunity:
Electrostatic Discharge (ESD)
Fast Transient-Burst
Conducted Radio-Frequency Common Mode
Surge Immunity
Radio-Frequency Electromagnetic Field
3-28
Table 3.7 - Emission and immunity levels
Basic Standard
IEC/EN61800-3 (2004)
Refer to the table 3.8.
IEC 61000-4-2 (1995)
4 kV for contact discharge and 8 kV for air discharge.
+A1 (1998) +A2 (2001)
2 kV / 5 kHz (coupling capacitor) power input cables;
IEC 61000-4-4 (1995)
1 kV / 5 kHz control cables, and remote keypad cables;
+A1 (2000) +A2 (2001)
2 kV / 5 kHz (coupling capacitor) motor output cables.
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz).
IEC 61000-4-6 (2003)
Motor input cables, control cables, and remote keypad cables.
1.2/50 μs, 8/20 μs;
IEC 61000-4-5 (1995)
1 kV line-to-line coupling;
2 kV line-to-ground coupling.
80 to 1000 MHz;
IEC 61000-4-3 (2002)
10 V/m;
80 % AM (1 kHz).
Level

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents