Multiple Devices; Switched Voltage Output; Switched 5 Vdc; Switched 12 Vdc - Campbell CDM-A100 Series Instruction Manual

Table of Contents

Advertisement

8.3

Multiple Devices

NOTE
8.4

Switched Voltage Output

8.4.1 Switched 5 Vdc

8.4.2 Switched 12 Vdc

9.

Maintenance

9.1

Factory Calibration or Repair Procedure

Multiple CDMs may be connected to a single datalogger using a daisy-chain or
star topology (see Section 7.6, Connecting Multiple CDMs
network configurations, as total cable length increases, the maximum possible
bit rate decreases. Limitations on cable length and baud rate are examined in
the document
Designing Physical Network Layouts for the CPI
available at www.campbellsci.com/app-notes.
When including two or more CDM-A100 devices in the program, the
processing mode of the datalogger affects the measurement timing of each
CDM-A100. In
sequential
mode, the CDM-A100 devices make measurements
one after the other, following the order of their instructions within the program.
Conversely, in
pipeline
mode, the devices start their measurements
simultaneously. Pipeline mode is recommended.
In either mode, measurements that require excitation MUST be
made on the same CDM-A100 that provides the excitation voltage
or current.
An SW5V terminal is normally used to operate an external relay-driver circuit
because the port itself has limited drive capacity. Drive capacity is determined
by the 5 Vdc supply, a Schottky diode, and a 30 Ω output resistance. It is
expressed as:
= 5 V – 0.3 V – (30 Ω) x I
V
0
Where V
is the drive limit, and I
0
device. FIGURE 6-1, Current sourcing on SW5V terminals
relationship between supply voltage and current load.
The SW12V terminals are used to power devices such as sensors that require
12 Vdc during measurement. Current sourcing must be limited to 200 mA or
less on each channel. When the supply voltage is below 14.5 Vdc, the voltage
on the SW12V terminals track the power supply. Voltage on these terminals is
regulated to 12.5 ± 0.5 Vdc when the supply voltage is 14.5 to 32 Vdc.
Protect the CDM-A100 from humidity and moisture.
Send to Campbell Scientific for factory calibration every three years.
If sending the CDM-A100 to Campbell Scientific for calibration or repair,
consult first with a Campbell Scientific representative. If the CDM-A100 is
malfunctioning, be prepared to perform some troubleshooting procedures while
on the phone with Campbell Scientific. Many problems can be resolved with a
0
is the current required by the external
0
CDM-A100 Series
). In both
(p. 21)
Bus, which is
, shows the
(p. 16)
29