Par
Variable name
1
USER CONTROL
2
HOME ANTIFREEZE T°
3
FREQ REDUCT
4
ROOM HYSTERESIS
5
ADJUST T° ZONES
6
DAY PERIOD
7
TROOM SENSOR ADJ ZONES
Use DAYS
button to select below mentioned functions
0. Home Antifreeze option
0: Disable
1: Enable
1. Silent Mode
0: Not Active
1: Active
2. Power off all the electric heater
0: Operating as normal
1: Electric heater disable
3. Specifies if domestic hot water is produced despite sensor diagnostics or disinfection
cycle failure
The code is automatically reset to 0 when the above problem is solved
0: No
1: Yes
4. Specifies whether activation of the backup (for heating) or booster (for DHW) heating
elements is permitted when the external unit has an alarm.
0: No
1: Yes
5. Domestic hot water BOOSTER: Allows to heat up domestic hot water electric heater
regardless the heater schedule
The code is automatically reset to 0 once the domestic hot water setpoint is reached
0. Domestic hot water heater is turned on, if needed, according to the schedule
1. Domestic hot water heater is turned on, if needed, regardless the schedule
6. Water Pump Management zone 0, 1
0. Water pump of zone 0, 1 does not stop when room 0, 1 set point is reached
1. Water pump of zone 0, 1 stops when room 0, 1 setpoint is reached
7. Water Pump Management zone 2
0. Water pump of zone 2 does not stop when room 2 setpoint is reached
1. Water pump of zone 2 stops when room 2 setpoint is reached
Home antifreeze threshold T° value
Value of the outdoor unit frequency reduction in %
Hysteresis on room temperature (see thermostat function)
Modifies maximum temperature of heating climatic curve and minimum temperature
of cooling climatic curve.
Use DAYS
button to select below mentioned functions
0. Water set point adjustment in Heat mode for zone 0, 1
1. Water set point adjustment in Heat mode for zone 2
2. Water set point adjustment in Cool mode for zone 0, 1
3. Water set point adjustment in Cool mode for zone 2
User can select how many periods per day is available for the scheduling.
Use DAYS
button to select below mentioned functions
Day 0 - Zone 0, 1 and 2 schedule
0. no schedule; Schedule Icon will not be displayed
1. 2 periods
2. 4 periods
3. 6 periods
Day 1 - Domestic hot water schedule
1. 2 periods
2. 4 periods
Use DAYS
button to select below mentioned functions:
0. Room temperature sensor adjustment for zone 0, 1
1. Room temperature sensor adjustment for zone 2
EN
Description
82
82
Value range
Default
Min
Max
1
0
0
0
0
1
0
0
0
0
6 °C
12 °C
6 °C
50%
100%
100%
0,1
2
0,5
-5 °C
+5 °C
0 °C
3
1
3
2
-5 °C
+5 °C
0 °C