Control Units
2) X0 through X5 are inputs for the high-speed counter and have
a fast response time. If used as normal inputs, we recommend
inserting a timer in the ladder program as chattering and noise
may be interpreted as an input signal.
Limitations on Number of Simultaneous Input ON Points
Keep the number of input points per common which are simultaneously ON within the
following range as determined by the temperature.
FP0–C14RS/C14CRS
8
Number of
input points
per common
5
which are
simultaneously
3
ON
Ambient temperature (5C/5F)
FP0–C16T/C16CT/C16P/C16CP
8
Number of
input points
per common
which are
4
simultaneously
ON
Ambient temperature (5C/5F)
FP0–C32T/C32CT/C32P/C32CP/T32CP
16
Number of
input points
per common
which are
8
6
simultaneously
ON
Ambient temperature (5C/5F)
2-12
at 24V DC
at 26.4V DC
35/
45/
55/
95
113
131
at 26.4V DC
at 24V DC
45/
50/
55/
113
122
131
at 26.4V DC
at 24V DC
23/
31/
55/
73.4
87.8
131
Matsushita Electric Works (Europe) AG
FP0 Hardware