2.4.6 Serial Communication

Connect RS-485 serial communication wiring to terminals
(+)68 and (-)69.
A shielded serial communication cable is
recommended
See 2.4.2 Grounding Requirements for proper
grounding
61
68
69
Figure 2.22 Serial Communication Wiring Diagram
®
VLT
AQUA Drive
Instruction Manual
Output
relay
02
01
Command Circuit
220Vac
Output
A1
Frewheeling
Contactor
diode
Input
A2
Power Circuit
380Vac
+
RS-485
®
MG20M922 - VLT
is a registered Danfoss trademark
For basic serial communication set-up, select the following
1.
Protocol type in 8-30 Protocol.
2.
Adjustable frequency drive address in
8-31 Address.
3.
Baud rate in 8-32 Baud Rate.
Four communication protocols are internal to the
adjustable frequency drive. Follow the motor
manufacturer wiring requirements.
Danfoss FC
Modbus RTU
Johnson Controls N2
Functions can be programmed remotely using
the protocol software and RS-485 connection or
in parameter group 8-** Communications and
Options.
Selecting a specific communication protocol
changes various default parameter settings to
match that protocol's specifications along with
making additional protocol-specific parameters
available
Option cards for the adjustable frequency drive
are available to provide additional communi-
cation protocols. See the option-card
documentation for installation and instruction
manual
2
®
2-13