Danfoss VLT AQUA Drive FC 202 Instruction Manual page 56

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Application Set-up Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
6
6
55
A OUT
42
COM
39
U - I
A53
Table 6.4 Analog Speed Reference (Voltage)
NOTE!
Note switch setting for selecting voltage or current.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.5 Analog Speed Reference (Current)
6-2
®
VLT
AQUA Drive
Instruction Manual
Parameters
Function
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
10 V*
High Voltage
6-14 Terminal 53
0*
Low Ref./Feedb.
Value
6-15 Terminal 53
50*
High Ref./Feedb.
Value
+
* = Default Value
Notes/comments:
-
0 - 10V
Parameters
Function
6-12 Terminal 53
4 mA*
Low Current
6-13 Terminal 53
20 mA*
High Current
6-14 Terminal 53
0*
Low Ref./Feedb.
Value
6-15 Terminal 53
50*
High Ref./Feedb.
Value
+
* = Default Value
Notes/comments:
-
4 - 20mA
MG20M922 - VLT
NOTE!
Setting
Note switch setting for selecting voltage or current.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.6 Run/Stop Command with External Interlock
Setting
®
is a registered Danfoss trademark
Parameters
Function
Setting
5-10 Terminal 18
[8] Start*
Digital Input
5-12 Terminal 27
[7] External
Digital Input
Interlock
* = Default Value
Notes/comments: