Danfoss VLT AQUA Drive FC 202 Instruction Manual page 57

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Application Set-up Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 6.7 Run/Stop Command without External Interlock
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.8 External Alarm Reset
®
VLT
AQUA Drive
Instruction Manual
Parameters
Function
Setting
5-10 Terminal 18
[8] Start*
Digital Input
5-12 Terminal 27
[7] External
Digital Input
Interlock
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
Parameters
Function
Setting
5-11 Terminal 19
[1] Reset
Digital Input
* = Default Value
Notes/comments:
®
MG20M922 - VLT
is a registered Danfoss trademark
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
≈ 5kΩ
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.9 Speed Reference (using a manual potentiometer)
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 6.10 Run Permissive
Parameters
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
10 V*
High Voltage
6-14 Terminal 53
0*
Low Ref./Feedb.
Value
6-15 Terminal 53
50*
High Ref./Feedb.
Value
* = Default Value
Notes/comments:
Parameters
Function
Setting
5-10 Terminal 18
Digital Input
[8] Start*
5-11 Terminal 19
[52] Run
Digital Input
Permissive
5-12 Terminal 27
[7] External
Digital Input
Interlock
5-40 Function
[167] Start
Relay
command
act.
* = Default Value
Notes/comments:
6-3
6
6

Advertisement

Table of Contents
loading

Table of Contents