General Installation Information; Consideration; Hazardous Area Considerations; Installing Jdf300 Field Indicator - ABB JDF300 Operating Instruction

Field indicator with foundation fieldbus communication
Table of Contents

Advertisement

8
J D F 3 0 0 | F I E L D I N D I C ATO R | O I/ J D F 3 0 0 - E N R E V. B
. . .5 Installation

General installation information

Field indicator factory configuration consideration
The field indicator in your hands has been manufactured to
reflect the published specification. According to the user
requirements it is possible to customize TAG number and
device address.

Hazardous area considerations

The field indicator can be installed in hazardous area only if
certified. The certification plate is permanently fixed on the
field indicator housing. JDF300 can have the following
certifications:
INTRINSIC SAFETY Ex ia:
• ATEX Europe (code E1) approval
II 1 G Ex ia IIC T6...T4 Ga, II 1 D Ex ia IIIC T85 °C Da;
IP66, IP67.
• IECEx (code E8) approval
Ex ia IIC T6...T4 Ga, Ex ia IIIC T85 °C Da; IP66, IP67.
EXPLOSION PROOF:
• ATEX Europe (code E2) approval
II 2 G Ex db IIC T6 Gb Ta=–50 °C to +75 °C,
II 2 D Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C;
IP66, IP67.
• IECEx (code E9) approval
Ex db IIC T6 Gb Ta=–50 °C to +75 °C,
Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C; IP66, IP67.
INTRINSIC SAFETY Ex ic:
• ATEX Europe (code E3) type examination
II 3 G Ex ic IIC T6...T4 Gc, II 3 D Ex tc IIIC T85 °C Dc;
IP66, IP67.
• IECEx (code ER) type examination
Ex ic IIC T6...T4 Gc, Ex tc IIIC T85 °C Dc; IP66, IP67.
FM Approvals US (code E6) and
FM Approvals Canada (code E4):
• Explosionproof:
Class I, Division 1, Groups A, B, C, D; T4
• Dust-ignitionproof:
Class II, III Division 1, Groups E, F, G; T4
• Flameproof (US): Class I, Zone 1 AEx db IIC T4 Gb
• Flameproof (Canada): Class I, Zone 1 Ex db IIC T4 Gb
• Intrinsically safe:
Class I, Zone 0 AEx ia IIC T6...T4 Ga (US)
Class I, Zone 0 Ex ia IIC T6...T4 Ga (Canada)
Class I, Division 1, Groups A, B, C, D, T6...T4
Class II, Division 1, Groups E, F, G, T6...T4
Class III
when connected per drawing 3KXP000074U0109
"FISCO Field Instrument"
• Energy limited (US):
Class I, Zone 2 AEx nC IIC T6...T4 Gc
• Energy limited (Canada):
Class I, Zone 2 Ex nC IIC T6...T4 Gc
• Nonincendive: Class I, Division 2, Groups A, B, C, D T6...T4
when connected per drawing 3KXP000074U0109
"FISCO Field Instrument"
• Type 4X, IP66, IP67 for all above markings.
COMBINED ATEX (code EW = E1 + E2 + E3), (code E7 = E1 +
E2)
COMBINED IECEx (code EI = E8 + E9 + ER), (code EH = E8 +
E9)
COMBINED FM Approvals US and Canada
• Intrinsically safe (code EA)
• Explosionproof, Dust-ignitionproof (code EB)
• Nonincendive (code EC)
COMBINED ATEX, FM and IECEx Approvals (code EN)
WARNING
Model JDF300 enclosure contains aluminium and is
considered to present a potential risk of ignition by impact or
friction. Care must be taken into account during installation
and use to prevent impact or friction.

Installing JDF300 field indicator

The field indicator model JDF300 can be mounted directly a
wall using approriate fixing screws (not provided by the
manufacturer).
A mounting bracket for pipe mounting (2 in pipe) is also
available as an accessory. It is recommended to mount the
field indicator to prevent this from being source of possible
damage for unskilled operators.

Bracket mounting

Mounting bracket is available as standard please refer to
the relevant installation drawing below in mm (inch.):
Figure 4 Mounting bracket

Advertisement

Table of Contents
loading

Table of Contents