Mao Block Mapping - ABB JDF300 Operating Instruction

Field indicator with foundation fieldbus communication
Table of Contents

Advertisement

J D F 3 0 0 | F I E L D I N D I C ATO R | O I/ J D F 3 0 0 - E N R E V. B

MAO Block Mapping

Idx
Parameter
0
BLOCK_OBJ
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
TARGET
ACTUAL
5
MODE_BLK
PERMITTED
NORMAL
6
BLOCK_ERR
7
CHANNEL
8
IN1
9
IN2
10
IN3
11
IN4
12
IN5
13
IN6
14
IN7
15
IN8
16
MO_OPTS
17
FSTATE_TIME
18
FSTATE_VAL1
19
FSTATE_VAL2
20
FSTATE_VAL3
21
FSTATE_VAL4
22
FSTATE_VAL5
23
FSTATE_VAL6
24
FSTATE_VAL7
25
FSTATE_VAL8
26
FSTATE_STATUS
27
UPDATE_EVT
28
BLOCK_ALM
Description / Range / Selections / Notes
In the Block Object data structure, there are different items describing the block characteristics. Execution period,
Number of parameters in the block, the DD Revision, Profile Revision, View Objects characteristics and so on
The revision level of the Static data associated with the Function Block. The revision level is incremented each time a
static parameter value (S – under Storage) in the block is changed.
The user description of the intended application of the block
The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
AUTO / OOS
//
AUTO / OOS
AUTO
Bit 0 = Other
Bit 1 = Configuration Error
Bit 15 = Out of Service
0:
Uninitialized
1 - 8:INPUT n selection
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
All set to 0 (not used in the JDF300)
Default = 0  not used
Default = 0  not used
Default = 0  not used
Default = 0  not used
Default = 0  not used
Default = 0  not used
Default = 0  not used
Default = 0  not used
Default = 0  not used
Not used in the JDF300
This alert is generated by any change to the static data
The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The
cause of the alert is entered in the subcode field. The first alert to become active will set the Active Status in the
status parameter. As soon as the Unreported status is cleared by the alert reporting task, another block alert may
be reported without clearing the Active Status, if the subcode has changed
The selectable modes by the operator.
The mode the block is currently in.
Allowed modes that the target may take on
The common mode for the Actual.
MAO Not Scheduled
MAO.Channel = 0 (Uninitialized)
** Doesn't allow at the MAO to move out from OOS
CHANNEL = 1 (default)
Floating Point value + Status
NOT USED in the JDF300
25