ABB JDF300 Operating Instruction page 36

Field indicator with foundation fieldbus communication
Table of Contents

Advertisement

36
J D F 3 0 0 | F I E L D I N D I C ATO R | O I/ J D F 3 0 0 - E N R E V. B
Idx
Parameter
13
INPUT_OPTS
14
IN
15
IN_LO
16
IN_1
17
IN_2
18
IN_3
19
RANGE_HI
20
RANGE_LO
21
BIAS_IN_1
22
GAIN_IN_1
23
BIAS_IN_2
24
GAIN_IN_2
25
BIAS_IN_3
26
GAIN_IN_3
27
COMP_HI_LIM
28
COMP_LO_LIM
29
ARTH_TYPE
30
BAL_TIME
31
BIAS
32
GAIN
33
OUT_HI_LIM
34
OUT_LO_LIM
35
UPDATE_EVT
36
BLOCK_ALM
Description / Range / Selections / Notes
Options the user may select to alter the calculation done in a control loop
Bit 0
IN Use uncertain as good
Bit 1
IN_LO Use uncertain as good
Bit 2
IN_1 Use uncertain as good
Bit 3
IN_1 Use bad as good
Bit 4
IN_2 Use uncertain as good
Bit 5
IN_2 Use bad as good
Bit 6
IN_3 Use uncertain as good
Bit 7
IN_3 Use bad as good
The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
Input for the low range transmitter, in a range extension application. Expressed in PV_SCALE Unit
The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
Constant Value above which the range extension has switched to the high range transmitter Expressed in PV_SCALE
Unit
Constant Value below which the range extension has switched to the low range transmitter Expressed in PV_SCALE
Unit
The constant to be added to IN_1
The constant to be multiplied times (IN_1 + Bias)
The constant to be added to IN_2
The constant to be multiplied times (IN_2 + Bias)
The constant to be added to IN_3
The constant to be multiplied times (IN_3 + Bias)
The high limit imposed on the PV compensation term. Expressed in PV_SCALE Unit Code
The low limit imposed on the PV compensation term. Expressed in PV_SCALE Unit Code
The identification number of the arithmetic algorithm
1
Flow Compensation, Linear
2
Flow Compensation, Square Root
3
Flow Compensation, Approximate
4
BTU Flow
5
Traditional Multiple Divide
6
Average
7
Traditional Summer
8
Fourth Order Polynomial
9
Simple HTG compensated Level
Acceptable value: OUT_SCALE +/- 10%
Expressed in OUT_SCALE Unit
Expressed in OUT_SCALE Unit
0 or > 0
Acceptable value: OUT_SCALE +/- 10%
Expressed in OUT_SCALE Unit
This alert is generated by any change to the static data
The block alarm is used for all configuration, hardware, connection failure or system problems in the block.
The cause of the alert is entered in the subcode field. The first alert to become active will set the Active Status in the
status parameter. As soon as the Unreported status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active Status, if the subcode has changed
The specified time for the internal working value of bias to
return to operator set bias. Also used to specify the time
constant at which the integral term will move to obtain
balance when the output is limited and the mode is AUTO,
CAS, or RCAS. Expressed in seconds
The bias value used in computing the function block
output
Dimensionless value used by the block algorithm in
calculating the block output
Limits the maximum output value.
Limits the minimum output value.