J D F 3 0 0 | F I E L D I N D I C ATO R | O I/ J D F 3 0 0 - E N R E V. B

Block Mapping

Idx
Parameter
0
BLOCK_OBJ
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
TARGET
ACTUAL
5
MODE_BLK
PERMITTED
NORMAL
6
BLOCK_ERR
7
PV
8
SP
9
OUT
10
PV_SCALE
11
OUT_SCALE
12
GRANT_DENY
13
CONTROL_OPTS
14
STATUS_OPTS
15
IN
16
PV_FTIME
Description / Range / Selections / Notes
In the Block Object data structure, there are different items describing the block characteristics. Execution period,
Number of parameters in the block, the DD Revision, Profile Revision, View Objects characteristics and so on
The revision level of the Static data associated with the Function Block. The revision level is incremented each time a
static parameter value (S – under Storage) in the block is changed.
The user description of the intended application of the block
The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
AUTO / MAN / CAS / RCAS / ROUT / OOS
AUTO / MAN / OOS / IMAN / CAS / RCAS / ROUT / LO
AUTO / CAS
This parameter reflects the error status associated with the hardware or software components associated with a
block. It is a bit string, so that multiple errors may be shown.
The process variable used in block execution, expressed in PV_SCALE unit Code
The analog Set Point value of this block, expressed in
PV_SCALE Unit Code
The block output value calculated as a result of the block
execution, expressed in OUT_SCALE unit code
The high and low scale values, engineering units code, and number of digits to the right of the decimal point to be
used in displaying the PV parameter and parameters which have the same scaling as PV.
The high and low scale values, engineering units code, and number of digits to the right of the decimal point to be
used in displaying the OUT parameter and parameters which have the same scaling as OUT.
Options for controlling access of host computer and local control panels to operating, tuning and alarm parameters
of the block.
Options the user may select to alter the calculation done in a control loop
Bit 0
Bypass Enable
Bit 1
SP-PV Track in Man
Bit 2
SP-PV Track in ROut
Bit 3
SP-PV Track in LO or IMan
Bit 4
SP Track retained target
Bit 5
Direct Acting
Bit 6
Track if Bad TRK_IN_D
Bit 7
Track Enable
Bit 8
Track in Manual
Bit 9
Use PV for BKCAL_OUT
Bit 12
Obey limits if CAS or RCAS
Bit 13
No out limits in Manual
Options which the user can select for the block processing of status. The available selections are:
Bit 0
Initiate Fault State if BAD IN
Bit 1
Initiate Fault State if BAD CAS_IN
Bit 2
Use Uncertain as Good
Bit 5
Target to Manual if BAD IN
Bit 9
Target AUTO if BAD CAS_IN
Bit 10
Target to Man if BAD TRK_IN_D
Bit 11
IFS if BAD TRK_IN_D
The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
0 to 60 seconds
The selectable modes by the operator.
The mode the block is currently in.
Allowed modes that the target may take on
The common mode for the Actual.
Acceptable value: PV_SCALE +/- 10%
Writeable only if MODE_BLK .ACTUAL = MAN
Time constant of a single exponential filter for the PV,
expressed in seconds. This is the time necessary for reach
the 63% of the variation in input.
29