Optional Wired-On Sst Plate (I1); Handling And Storage; Installation; General - ABB JDF300 Operating Instruction

Field indicator with foundation fieldbus communication
Table of Contents

Advertisement

J D F 3 0 0 | F I E L D I N D I C ATO R | O I/ J D F 3 0 0 - E N R E V. B
JDF300 field indicator is in compliance with EMC 2014/30/EU.
The certification plate (ref.A) shown here is issued by ABB S.p.A,
22016 Tremezzina, Italy, with the numbers:
• FM 18 ATEX 0054X Ex db
• FM 18 ATEX 0055X Ex ia
• FM 18 ATEX 0056X Ex ic
• IECEx FME 18.0004X Exia, Ex db, Ex ic
• FM 18 US 0231X (IS, XP, NI, DIP) US
• FM 18 US 0110X (IS, XP, NI, DIP) CAN

Optional wired-on SST plate (I1)

The JDF300 can be supplied with the optional "Wired
on stainless steel plate" (figure 3) which is permanently laser
printed with a custom text specified in phase of order. The
available space consists in 4 lines with 32 characters per line.
The plate will be connected to the field indicator with a
stainless steel wire.
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD
Figure 3 4 -line layout of the optional wired-on Stainless Steel
plate

4 Handling and Storage

The instrument does not require any special precautions during
handling although normal good practice should be observed.
The instrument does not require any special treatment if stored
as dispatched and within the specified ambient conditions.
There is no limit to the storage period, although the terms of
guarantee remain as agreed with the Company and as given in
the order acknowledgement.
Model JDF300
Storage temperature limits
With LCD display
–40 and 85 °C (–40 and 185 °F)

5 Installation

General

Study these installation instructions carefully before
proceeding.
Failure to observe the warnings and instructions may cause a
malfunction or personal hazard. Before installing the field
indicator, check whether the device design meets the
requirements of the measuring point from a measurement
technology and safety point of view. This applies in respect of:
• Environment corrosion
• Explosion protection certification
• Temperature
• Operating voltage and current
In addition, the relevant directives, regulations, standards, and
accident prevention regulations must be observed (e.g., VDE/
VDI 3512, DIN 19210, VBG, Elex V, etc.). As far as possible, the
setup should be free from critical ambient conditions such as
extreme temperatures, vibrations, or shocks.
IMPORTANT
If unfavorable ambient conditions cannot be
avoided for reasons relating to building structure,
measurement technology, or other issues, product
quality may be affected.
IP protection & designation
The field indicator is dust and sand tight and protected against
spray water effect as defined by IEC60529 to IP66, IP67 or by
NEMA 250 Type 4X.
The first number indicates the protection of the electronics
against the entry of foreign bodies, including dust.
"6" means that the housing is dust-proof (i.e., no ingress of
dust). The second number indicates the type of protection
the integrated electronics have against the effects of
temporary immersion in water under standardized water
pressure and temporal conditions.
7