ABB JDF300 Operating Instruction page 21

Field indicator with foundation fieldbus communication
Table of Contents

Advertisement

J D F 3 0 0 | F I E L D I N D I C ATO R | O I/ J D F 3 0 0 - E N R E V. B
Idx
Parameter
59
FD_FAIL_ALM
60
FD_OFFSPEC_ALM
61
FD_MAINT_ALM
62
FD_CHECK_ALM
63
FD_FAIL_PRI
64
FD_OFFSPEC_PRI
65
FD_MAINT_PRI
66
FD_CHECK_PRI
67
FD_SIMULATE
68
FD_RECOMMEN_ACT
69
SPECIAL_RESTART
70
SPECIAL_OPERATION
71
MESSAGE
72
DESCRIPTOR
73
INSTALLATION_DATE
74
LOCAL_OPERATIONS
75
DEVICE_SER_NUM
Description / Range / Selections / Notes
Fail Alarm Object
Out of Spec Alarm Object
Maintenance Alarm Object
Function Check Alarm Object
Fail error priority
Out of Spec error priority
Maintenance error priority
Function Check error priority
Disabled by default
Code identifying what should be done to alleviate the anomalous condition. In case of more error conditions
detected, this code refers to the most severe/critical
0 is defined as Not Initialized, 1 is defined as No Action Required, all others defined by manufacturer
Bit 11
AR pre-setting
Bit 12
IS pre-setting
Bit 14
PID1 pre-setting
Bit 23
PID2 pre-setting
Bit 25
CS pre-setting
Bit 29
MAO-pre-setting
Bit 30
RB pre-setting
0
Do nothing
Message
Descriptor
Installation date
0
disabled
1
Enabled (default)
Serial Number of the Field indicator as printed on the main Type Plate (on the housing) and to be used as final part
of the DEV_ID
The simulation can be enabled only if the SW4 of the
electronics is moved to Simulation Enable position
After the selection of one or more blocks of this list is
written to SPECIAL_RESTART, then the operation is really
executed writing the command "Special Restart" in the
RB_RESTART.
All the selected Blocks are configured to a pre-defined
setting allowing their switching to AUTO Mode.
PS: The Function Blocks must have been previously
instantiated into a Function Block Application otherwise
cannot move out from OOS.
No Special Operations available in the JDF300
Local operation via PUSH BUTTONS are not allowed
Local operation via PUSH BUTTONS are allowed