13 Requirements for installation and use in US and Canada

General

IMPORTANT
Note for field indicator with combined approval
Before installation of the field indicator, the customer should
permanent mark his chosen Protection Concept on the safety
label. The field indicator can only be used with according to
this Protection Concept for the whole life. If two or more
types of protection box (on safety label) are permanent
marked, the field indicator must be removed from hazardous
classified locations. The selected Type of Protection is
allowed to be changed only by manufacturer after a new
satisfactory assessment.

Environmental Conditions

JDF300 is designed to be safe under the following conditions:
• Outdoor use
• Altitude up to 2000 m
• Mains supply voltage fluctuation up to ± 10% of the
nominal voltage
• No temporary overvoltages occurring on the mains supply
• Pollution degree 2
• Maximum relative humidity 80 % for temperatures up to
31°C decreasing linearly to 50 % relative humidity at 40 °C
• Transient overvoltages up to the levels of Overvoltage
Category II
WARNING
No repair is allowed in all JDF300 flameproof joints: threads
of enclosure, covers and plugs. Consult the manufacturer if
repair of the flameproof joint is necessary.

Instructions for cleaning

Clean the external enclosure with soft rag and, if it is necessary,
use mild cleaning solution and rains with clear water.
If deposits are expected to accumulate, the equipment should
be cleaned on a regular basis, in accordance with the operating
conditions. Cleaning should ideally be carried out in a
workshop.
Insulation for secondary circuits derived from MAINS
CIRCUITS of OVERVOLTAGE CATEGORY II up to 300 V
The power supply of the loop must be achieved by a
transformer in which the primary windings are separated from
the secondary windings by REINFORCED INSULATION, DOUBLE
INSULATION or a sceen connected to the PROTECTIVE
CONDUCTOR TERMINAL.

Ex Safety aspects and IP Protection (USA)

Applicable standards

According to FM here is the list of Standards which can assure
compliance with Essential Safety Requirements
Standard
Description
3810
Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use, General
Requirements
3600
Electrical Equipment for use in Hazardous (Classified)
ANSI/ISA 60079-0
Locations, General Requirements
ANSI/ISA 60079-1
Electrical Equipment for use in Hazardous (Classified)
3615
Locations, protection by flameproof enclosures "d"
3610
Electrical Equipment for use in Hazardous (Classified)
ANSI/ISA 60079-11
Locations, protection by intrinsic safety "i"
3611
Electrical Equipment for use in Hazardous (Classified)
ANSI/ISA 60079-15
Locations, protection by intrinsic safety "n"
ANSI/ISA 60079-31
Electrical Equipment for use in Hazardous (Classified)
Locations, dust ignition protection by enclosure "t"

Classifications

The field indicator has been certified for the following Class,
Divisions and Gas groups, hazardous classified locations,
temperature class and types of protection.
• Explosionproof (US) for Class I, Division 1, Groups A, B, C and
D, hazardous (classified) locations, Class I Zone 1 AEx db IIC
T4 Gb, as Ex db type of protection.
• Dust ignition proof for Class II, III Division 1, Groups E, F and
G, hazardous (classified) locations, as Ex tb type of
protection.
• NonIncendive for Class I, Division 2, Groups A, B, C and D, in
accordance with Nonincendive field wiring requirements for
hazardous (classified) locations, as Ex ic type of protection.
• Intrinsically Safe for use in Class I, II and III, Division 1, Groups
A, B, C, D, E, F and G in accordance with Entity requirements
for hazardous (classified) locations, as Ex ia and Ex iaD type
of protection.
• Temperature class T4 to T6 (dependent on the maximum
input current and the maximum ambient temperature). See
following table for reference.
• Ambient Temperature range -40°C to +85°C (dependent on
the maximum input current and the maximum temperature
class).
• Type 4X applications Indoors/Outdoors, IP66, IP67.
For a correct installation in field of JDF300 field indicator
please see the related control drawing No 3KXP000074U0109.