. . .13 Requirements for installation and use in US and Canada

Special conditions

Installation cables suitable for specific maximum temperature
are indicated in the table here below:
Tamb
Power supply Cable type
Type of protection AEx tb and AEx db
-50°C up to +75°C
Up to 100mA
Type of protection AEx nC
-50°C up to +75°C
Up to 100mA
-50°C up to +70°C
Up to 160mA
-50°C up to +40°C Up to 40mA
The ambient temperature is not indicated on the label but on
this user manual.
The enclosure can be made in aluminium. The installation of the
equipment must take this into account with respect of impact
and friction sparking for it to be suitable for Group II fro EPL Ga.
That is not indicated on the label but only in this user manual.
The final user can chose the level of protection of the equipment
when the equipment is with the option E7, EW, E4, E6, EH, EI or
EN on the type of code for Hazardous areas certifications. When
the selection is made, it is not possible to change it. The same
procedure has to apply for all other codes when it is present a
multiple choice for the type of protection.
IMPORTANT
When installed with a conduit, a seal shall be installed within
50mm of the enclosure.

Ex Safety aspects and IP Protection (Canada)

Applicable standards

According to FM 18 CA 0110X here is the list of Standards which
can assure compliance with Essential Safety Requirements
Standard
Description
CSA 61010-1
Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use, General
Requirements
CSA 60079-0
Electrical Equipment for use in Hazardous (Classified)
Locations, General Requirements
CSA 60079-1
Electrical Equipment for use in Hazardous (Classified)
Locations, protection by flameproof enclosures "d"
CSA 60079-11 Electrical Equipment for use in Hazardous (Classified)
Locations, protection by intrinsic safety "i"
CSA 60079-15 Electrical Equipment for use in Hazardous (Classified)
Locations, protection by intrinsic safety "n"
CSA 60079-31 Electrical Equipment for use in Hazardous (Classified)
Locations, dust ignition protection by enclosure "t"
Cables suitable for a temp of 77°C
Cables suitable for a temp of 77°C
Cables suitable for a temp of 72°C
All cable can be used

Classifications

The field indicator has been certified for the following Class,
Divisions and Gas groups, hazardous classified locations,
temperature class and types of protection.
• Explosionproof (Canada) for Class I, Division 1, Groups A, B, C
and D, hazardous (classified) locations, Class I Zone 1 Ex db IIC
T4 Gb, as Ex db type of protection.
• Dust ignition proof for Class II, III Division 1, Groups E, F and G,
hazardous (classified) locations, as Ex tb type of protection.
• NonIncendive for Class I, Division 2, Groups A, B, C and D, in
accordance with Nonincendive field wiring requirements for
hazardous (classified) locations, as Ex ic type of protection.
• Intrinsically Safe for use in Class I, II and III, Division 1, Groups
A, B, C, D, E, F and G in accordance with Entity requirements
for hazardous (classified) locations, as Ex ia and Ex iaD type of
protection.
• Temperature class T4 to T6 (dependent on the maximum input
current and the maximum ambient temperature). See
following table for reference.
• Ambient Temperature range -40°C to +85°C (dependent on
the maximum input current and the maximum temperature
class).
• Type 4X applications Indoors/Outdoors, IP66, IP67.
For a correct installation in field of JDF300 field indicator
please see the related control drawing No 3KXP000074U0109.
Special conditions
Installation cables suitable for specific maximum temperature
are indicated in the table here below:
Tamb
Power supply
Type of protection AEx tb and AEx db
-50°C up to +75°C Up to 100mA
Type of protection AEx nC
-50°C up to +75°C Up to 100mA
-50°C up to +70°C Up to 160mA
-50°C up to +40°C Up to 40mA
The ambient temperature is not indicated on the label but on
this user manual.
The enclosure can be made in aluminium. The installation of the
equipment must take this into account with respect of impact
and friction sparking for it to be suitable dor Group II fro EPL
Ga. That is not indicated on the label but only in this user
manual.
The final user can chose the level ofprotection of the equipment
when the equipment is with the option E5, EJ, EK or EL on the
type of code for Hazardous areas certifications. When the
selection is made, it is not possible to change it. The same
procedure has to apply for all other codes when it is present a
multiple choice for the type of protection.
IMPORTANT
When installed with a conduit, a seal shall be installed within
50mm of the enclosure.
Cable type
Cables suitable for a temp of 77°C
Cables suitable for a temp of 77°C
Cables suitable for a temp of 72°C
All cable can be used