The following figures and tables provide specifications for each Unit of the C200H. I/O Units may take on one of
three different shapes and are sometimes referred to as A-shape Units, B-shape Units, or E-shape Units. Group-2
High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape Units or
D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these five
shapes of I/O Unit.
CPU Units and Power Supplies
General Specifications
Item
Supply Voltage
Operating Voltage Range
Power Consumption
Surge Current
Output Capacity
Fuse
24 VDC Output
Insulation Resistance*
Dielectric Strength*
Noise Immunity
Vibration
Shock
Ambient Temperature
Humidity
Atmosphere
Grounding
Enclosure Rating
Weight
!
Caution
*Internal components might be damaged if insulation resistance or dielectric strength tests for the
AC power supply are repeated many times with the LG and GR terminals connected. Do not con-
duct a dielectric strength test on the C200H-CPU23-E, PS211, RT002-P, or RT202 Units. The
power supply input line and internal circuit of the 24 VDC Power Supply are not isolated from each
other; do not conduct insulation resistance or dielectric strength tests. If an insulation resistance
test or dielectric strength test over 50 VDC is conducted, the Power Supply will be damaged.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Appendix B
Specifications
C200H-CPU21-E/CPU31-E, PS221
100 to 120/200 to 240 VAC selectable
50/60 Hz
85 to 132/170 to 264 VAC
120 VA max.
30 A max.
CPU-21-E: 4.6 A 5 VDC (3.2 A supplied to I/O Units)
CPU-23-E: 3 A 5 VDC (1.6 A supplied to I/O Units)
CPU-31-E: 4.6 A 5 VDC (3.0 A supplied to I/O Units)
Expansion I/O Rack: 3 A 5 VDC (2.7 A supplied to I/O Units)
2 A 250 V 5.2 dia. x 20 (MF51NR)
+10%
0.3 A 24 VDC
/
–20%
20 MΩ between AC terminals and the GR
terminal at 500 VDC
2,000 VAC 50/60 Hz for 1 minute between AC terminals and housing 500 VAC 50/60 Hz
for 1 minute between DC terminals and housing Leakage current: 10 mA max.
1,500 Vp-p, pulse width: 100 ns to 1 µs, rise time: 1 ns
Mechanical durability: 10 to 35 Hz, 1 mm double amplitude (24.5 m/s
directions, for 2 hours each (When mounted on DIN track, 16.7 Hz, 1 mm double
2
amplitude (4.9 m/s
) in X, Y, and Z directions, for 1 hour each)
Malfunction durability: 2 to 55 Hz, 19.6 m/s
each (When mounted on DIN track, 2 to 55 Hz, 2.94 m/s
minutes each)
2
98 m/s
in X, Y, and Z directions, 3 times each
Operating: 0° to 55°C (0° to 45°C for Programming Console) Storage: –20° to 65°C
35% to 85% (without condensation)
Must be free of the following:
Corrosive gases
Abrupt temperature changes
Direct sunlight
Dust, salt, or metal filings
Water, oil, or chemicals
Less than 100 Ω
Mounted in a panel
6 kg max.
C200H-CPU23-E, PS211
24 VDC
20.4 to 26.4 VDC
40 W max.
30 A max.
2 A 125 V 5.2 dia. x 20 (MF51NR)
None
See caution.
2
) in X, Y, and Z
2
, in X, Y, and Z directions, for 20 minutes
2
, in X, Y, and Z directions, for 20
83