Omron SYSMAC C200H Installation Manual page 146

Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

Specifications
5. The strobe signal has negative logic regardless of the setting of pin 5.
6. When the output device (such as a numeric display) does not have a pull-up resistor, it is necessary to
add a pull-up resistor between the + terminal of the power supply and each data (0 to 15) and strobe (0 to
15) terminal.
TTL I/O Unit C200H-MD501
(Used as I/O Unit with 16 Inputs and 16 Outputs)
Output Specifications (Connector 1)
Input Specifications (Connector 2)
General Specifications
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Fuses
Power for External Supply
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
High-speed Inputs
Internal Current Consumption
Weight
Dimensions
5 VDC±10% 35 mA (280 mA/common,
560 mA/Unit; output resistance 4.7 kΩ)
None
0.1 mA max.
0.4 V max.
0.2 ms max.
0.3 ms max.
2 (8 points/common)
2 (1 fuse/common; fuses are not user-replacable.)
20 mA 5 VDC min. (1.2 mA × no. of outputs ON)
5 VDC±10%
4.5 to 5.5 VDC
1.1 kΩ
3.5 mA (at 5 VDC)
3.0 VDC min.
1.0 VDC max.
2.5 ms/15 ms max. (switchable)
2.5 ms/15 ms max. (switchable)
2 (8 points/common)
8 points (connector 2 terminals 8 to 15, when set)
Pulse width: 1 ms/4 ms min. (switchable)
180 mA 5 VDC max.
300 g max.
130×34.5×100.5 (H×W×D, in millimeters)
Appendix B
139