Specifications
Terminal Connections
I/O word "n"
NC
NC
NC
COM1
15
14
5 VDC
13
+
12
+
11
10
9
8
Note 1. I/O word "n" is determined by the unit number setting (n = IR 100 + 10 × unit number).
2. When pin 2 of the Unit's DIP switch is ON, input points 08 to 15 in connector 2 are high-speed inputs.
DC Input Unit C200H-ID215 (32 Points)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
CN1
B
A
12
12
NC
11
11
NC
10
10
NC
COM0
9
9
7
8
8
6
7
7
5
5 VDC
6
6
+
4
5
5
+
3
4
4
2
3
3
1
2
2
0
1
1
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
High-speed Inputs
Internal Current Consumption
Weight
Dimensions
CN2
I/O word "n+1"
A
0
1
1
2
2
3
3
5 VDC
4
+
4
5
5
+
6
6
7
7
8
COM2
9
10
NC
11
NC
12
NC
24 VDC
20.4 to 26.4 VDC
5.6 kΩ
4.1 mA (at 24 VDC)
14.4 VDC min.
5.0 VDC max.
2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)
2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)
4 (8 points/common)
8 points (connector 2 terminals 8 to 15, when set)
Pulse width: 1 ms/4 ms min. (switchable)
130 mA 5 VDC max.
300 g max.
130×34.5×100.5 (H×W×D, in millimeters)
Appendix B
B
8
1
9
2
10
3
11
5 VDC
4
+
12
5
13
+
6
14
7
15
8
COM3
9
10
NC
11
NC
12
NC