Specifications
Connectable B7A Link Terminals
Input Terminals
Type
Screw terminals
Modular
PC connectors
Output Terminals
Type
Screw terminals
Modular
PC connectors
Note 1. Do not connect Terminals with different transmission delays to the same Interface Unit. Doing so will
cause a transmission error.
2. 10-point B7A Link Terminals and Mixed I/O (8 inputs/8 outputs) B7A Link Terminals cannot be con-
nected to a B7A Interface Unit. 16-point B7A Link Terminals, 32-point B7A Link Terminals with a two-cir-
cuit configuration, and Mixed I/O B7A Link Terminals with a 16-point input/output configuration can be
connected.
Comparison between Standard and Group-2 B7A Interface Units
Type
Models
Standard
C200H-B7AI1
C200H-B7AO2
Group-2
C200H-B7A12
C200H-B7A02
C200H-B7A21
C200H-B7A22
Note 1. Mount the B7A Interface Unit (C200H-B7AO1) to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Back-
plane.
2. 10-point B7A Link Terminals and Mixed I/O B7A Link Terminals with an 8 input-8 output configuration
cannot be connected to a B7A Interface Unit. 16-point B7A Link Terminals, 32-point B7A Link Terminals
with a two-circuit configuration, and Mixed I/O B7A Link Terminals with a 16-point input or output config-
uration can be connected.
3. Words IR 030 to IR 049 (Group-2 High-density I/O Unit and B7A Interface Unit Area) are allocated to the
inputs/outputs of Group-2 B7A Interface Units according to the setting of the I/O number switch on the
front of the Unit, in the way shown in the following table (for Mixed I/O Units, words are allocated in the
order output → input for each Unit).
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Model
B7A-T6j1
B7AS-T6j1
B7A-T6j6
B7AS-T6j6
B7A-T6D2
B7A-T6D7
B7A-TjE3
B7A-TjE8
Model
B7A-R6jj1
B7AS-R6jj1
B7A-R6jj6
B7AS-R6jj6
B7A-R6A52
B7A-R6A57
B7A-RjAj3
B7A-RjAj8
CPU Unit
Word allocations
Any C200H
Same as I/O
CPU Unit
Units (in order
mounted).
C200H-CPU21-
Words 030 to 049
E/22-E/23-E/
E/22-E/23-E/
allocated
allocated
31-E CPU Unit
according to I/O
only
only
number setting
number setting
(see note 3)
(same as Group-2
High-density I/O
Units)
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
Standard (19.2 ms)
High-speed (3 ms)
Standard (19.2 ms)
High-speed (3 ms)
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
Standard (19.2 ms)
High-speed (3 ms)
Standard (19.2 ms)
High-speed (3 ms)
Connectable B7A Link Terminals
Transmission
Transmission
delay
Standard
Input status
types only
held
(19.2 ms)
automatically
Standard
Switch setting
(19.2 ms) and
(19.2 ms) and
to hold or
to hold or
high-speed
reset Input
(3 ms) types
(3 ms) types
status.
status.
(set via
switch)
Appendix B
Points (see note
errors
2)
16-point
Terminals only
(10-point,
32-point, and
mixed I/O
Terminals cannot
be connected.
157