Omron SYSMAC C200H Installation Manual page 120

Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

Specifications
Transistor Output Unit C200H-OD411
Circuit Configuration
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.
Terminal Connections
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Internal
Fuse
circuit
Fuse blowout
detection circuit
F indicator
12 to 48 VDC
(1 A max., 3 A/Unit)
12 to 48 VDC 1 A (3 A/Unit)
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
1 (8 points/common)
140 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
30 mA 12 to 48 VDC min.
250 g max.
A-shape
OUT
L
V
OUT
L
COM
12 to 48 VDC
Fuse: GGS (Nagasawa)
5 A 125 V 5.2-dia × 20
0
A0
L
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM (OV)
12 to 48 VDC
A9
Appendix B
113

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpu21-eCpu23-eCpu31-e

Table of Contents