I/O Units
Setting the DIP Switch
Pin
Function
1
Operating mode
1
2
High-speed input
3
High-speed input
minimum pulse width
4
Input response time
4
5
Data output mode
6
Not used.
22
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
The operation of High-density I/O Units is controlled by setting the pins of the
DIP switch on the back panel. The following table shows the function of each pin
and applicable Units.
Applicable Units
C200H-OD501/OD215
C200H-MD501/MD115/MD215
C200H-ID501/ID215
C200H-MD501/MD115/MD215
C200H-ID501/ID215
2
C200H-MD501/MD115/MD215
3
C200H-ID501/ID215
C200H-MD501/MD115/MD215
C200H-OD501/OD215
---
Note
1. Used in the C200H-MD501/MD115/MD215 only when pin 1 is OFF, setting
the Unit to static mode.
2. Used in the C200H-ID501/215, C200H-MD501/MD215/MD115/MD215
only when pin 2 is ON, setting the Unit to High-speed input mode.
3. Sets the input response time for normal inputs. When pin 2 is ON, CN2 08 to
15 are pulse-catch inputs. Other inputs can be used as normal inputs.
4. Used when pin 1 is ON, setting the C200H-OD501/OD215 to dynamic out-
put mode.
Setting
ON
128 dynamic outputs
32 outputs
128 dynamic inputs
16 inputs, 16 outputs
Inputs 08 to 15 of CN2
Normal inputs
are high-speed inputs.
Inputs 08 to 15 of CN2
Normal inputs
are high-speed inputs.
4 ms
1 ms
15 ms max.
2.5 ms max.
Positive logic
Negative logic
---
---
I/O Unit locking notch
Nameplate
I/O indicators:
Indicate ON/OFF status of points
Unit number setting switch
24-pin connectors