Omron SYSMAC C200H Installation Manual page 103

Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

Specifications
Triac Output Unit C200H-OA222V
Circuit Configuration
Note No blown fuse detector circuit is provided.
Terminal Connections
96
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Internal
circuit
Fuse: 3 A 250 V (5.2-dia.x20) MF51SH (JIS)
250 VAC max.
(0.3 A max., 2 A/Unit)
0.3 A 250 VAC, 50/60 Hz (2 A/Unit)
10 mA (resistive load)/40 mA (inductive load)
10 VAC
3 mA (100 VAC) max./6 mA (200 VAC) max.
1.2 V max.
1/2 of load frequency or less.
1/2 of load frequency or less.
1 (12 points/common)
200 mA 5 VDC max.
3 A 250 V (5.2-dia.x20)
N/A
400 g max.
B-shape
OUT
L
OUT
L
Fuse
COM
250 VAC max.
0
B0
L
1
A0
L
2
B1
3
L
A1
L
4
B2
5
L
A2
L
6
B3
7
L
A3
8
L
B4
9
L
A4
10
L
B5
L
11
A5
L
B6
NC
A6
NC
B7
NC
NC
A7
B8
NC
COM
A8
B9
NC
Appendix B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpu21-eCpu23-eCpu31-e

Table of Contents