Specifications
Transistor Output Unit C200H-OD213
Circuit Configuration
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.
Terminal Connections
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
108
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Internal
Circuit
Fuse
Fuse blowout
detection circuit
F indicator
24 VDC
(2.1 A max., 5.2 A/Unit)
+10%
2.1 A 24 VDC
/
–15%
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
1 (8 points/common)
140 mA 5 VDC max.
8 A 125 V (5.2-dia.x20)
+10%
30 mA 24 VDC
250 g max.
A-shape
OUT
L
+ V
OUT
L
24 VDC
COM
Fuse: UL-TSC-8A-N1 (Nagasawa)
8 A 125 V 5.2-dia  20
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM (OV)
24 VDC
A9
Appendix B
(5.2 A/Unit) NPN output
/
min.
–15%