Note 1. I/O word "m" is determined by the I/O number setting (m = IR 030 + 2 × I/O number).
2. When the fuse blows, the F indicator lights and the error flag in AR 02 corresponding to the I/O number is
turned ON. I/O numbers 0 to 9 correspond to AR 0205 to AR 0214.
3. The interruption of power from the external power supply is treated the same as a fuse blowout.
4. Connect power supply wiring to every COM terminal, even though the COM terminals are connected
internally.
5. When wiring output circuits, be sure to use the correct polarity for the external power supplies. Wiring
with incorrect polarity may result in erroneous operation of the load.
Transistor Output Unit C200H-OD219 (64 Points)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
I/O word "m"
I/O word "m+1"
A
B
0
0
1
1
L
1
1
2
2
L
2
2
3
3
L
3
3
4
4
L
4
4
+
5
5
L
5
5
6
6
L
6
6
7
7
L
7
7
8
8
L
COM
9
9
10
10
8
8
11
11
L
9
9
12
12
L
10
10
13
13
L
11
11
14
14
L
12
12
+
15
15
L
13
13
16
16
L
14
14
17
17
L
15
15
18
18
L
COM
19
19
20
20
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuses
Power for External Supply
Weight
Dimensions
L
L
L
4.5 to 26.4 VDC
L
+
L
L
L
L
COM
L
L
L
L
+
L
L
L
L
COM
16 mA 4.5 VDC to 100 mA 26.4 VDC (see below)
None
0.1 mA max.
0.8 V max.
0.1 ms max.
0.4 ms max.
2 (32 points/common)
270 mA 5 VDC max.
Two 3.5 A fuses (1 fuse/common)
The fuses are not user-replacable.
220 mA 5 to 24 VDC±10% min.
(3.4 mA × number of ON pts)