Standard Application With Hart Functionality - ABB Endura ACA592-TC Operating Instructions Manual

Toroidal conductivity transmitter
Table of Contents

Advertisement

Endura ACA592
Toroidal conductivity transmitter

4.6.2 Standard Application with HART Functionality

Adding resistance R
250
 U
U
+ 0.022A x (R
Smin
Mmin
Where:
U
– Minimum operating voltage of transmitter
Mmin
(refer to technical data for transmitter)
U
– Minimum supply voltage of power supply/SPS input
Smin
(refer to technical data for transmitter)
R
– Line resistance between transmitter and power supply
Ltg
R
– Resistance for HART functionality
250
*Required
Fig. 4.7 Standard Application with HART Functionality
OI/ACA592/TC–EN Rev. B
increases the minimum supply voltage:
+ R
)
Ltg
250
Transmitter
+
U
R250*
Mmin
R
Ltg
4 Electrical Installation
Control Room
+
U
Smin
Power Supply /
SPS Input with Supply
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Endura aca592

Table of Contents