Dispenser Startup and Checklist (Cont'd)
Self-Contained
WARNING: If the lower door on the pulley side of the unit is off, close the door and lock it to
prevent injury.
1.
Verify that the motor voltage select switch on the self contained motor is in the proper position.
2. Turn on this products self contained pump motor circuit breaker. With the pump handle OFF, use a
voltmeter to verify 115/230 Volts AC power for the self contained pump motor by measuring
between the two black wires coming out of the electric reset. These wires should be connected to
the field wires for the pump motor power. If the motor is being operated off of 230 volts, this reading
will measure 230 Volts A.C. This products pump motor should not be running at this time.
3. Turn off this product's pump motor circuit breaker.
4. Repeat this test for any remaining dispensers.
All Dispensers
1. Turn off all circuit breakers.
2. Close and lock the lower doors and the upper doors.
3. Turn the circuit breaker for the system on.
4. Purge the air from the system.
5. Dispense a small amount of fuel from each hose to verify all positions are counting.
Proceed to the section for finishing the installation called "Potting Instructions".
Then proceed to the section titled "How to Calibrate the SB-100 Meter" .
22
107929 Rev E 04-24-17