6.4.6
Checking the operation readiness
All parameters are now set and defined according to the application.
1. Select: "Device" → "Download to device..." to download the parameters to the device.
2. Select "Execute even if the device TAG does not match the project data TAG." and click
View process values
The system is now ready for normal operation.
1. Select "View" → "Display" to see all measured process values.
2. Verify that the fields show the expected values.
Note
Measured Track Values
The "Measured Track Values" should show stable values within the normal range, i.e. the
gains should be stable values between 3 and 12 (smaller sizes low values and larger sizes
high values) and the actual velocities for the paths should be stable, constant and smoothly
changing values between 0 and 10 m/s.
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
Note
Before downloading the parameters, check that all listed data are loaded or changed and
in accordance with the application requirements.
"OK" to download all changes from the table to the device.
Commissioning
6.4 Commissioning via PDM
41