Checking The Operation Readiness - Siemens SITRANS F Operating Instructions Manual

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

6.5.9

Checking the operation readiness

All parameters are now set and defined according to the application.
1. Select: [Device → Download to device...] to download the parameters to the device.
Note
Before downloading the parameters, check that all listed data are loaded or changed and in
accordance with the application requirements.
2. Click [Start] to download all changes from the table to the device.
View process values
The system is now ready for normal operation.
1. Select [View → Process Variables] to see all measured process values.
2. Verify that the fields show the expected values.
Note
Measured Track Values
The Measured Track Values should show stable values within the normal range, i.e. the gains
should be stable values between 3 and 12 (smaller sizes low values and larger sizes high
values) and the actual velocities for the paths should be stable, constant and smoothly
changing values between 0 and 10 m/s.
SITRANS FUS380/FUE380
Operating Instructions, 05/2018, A5E00730100-AE
Commissioning
6.5 Commissioning via PDM