Siemens SITRANS FUS080 Operating Instructions Manual page 61

Ultrasonic flowmeters
Table of Contents

Advertisement

Gain step error conditions
Condition
15
High values
Unstable/fluctuating values
Δ gain step between path 1 and path 2 > 1
(2-path systems only)
In case of angular misalignment between transducer faces, the gain step will increase as
shown in the table below:
Angular misalignment
Flow velocity error conditions
Condition
Δ flow velocity values (between path 1 and path
2) > 1
(2-path systems only)
Unstable/fluctuating values
The actual velocities for the paths should be stable, constant and smoothly changing values
between 0 and 10 m/s.
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
9.2 Diagnosing with PDM
Cause
No transducer (e.g. defective cable)
Empty pipe
High damping (e.g. inhomogeneous media)
Unsuitable medium
Path angular misalignment
Air bubbles or solids in medium
Bad inlet conditions
Bad inlet conditions
Inhomogeneous medium
Path angular misalignment
Gain step increase
1
2
3
5
Cause
Bad inlet conditions (the higher the delta, the
worse the inlet conditions)
Disturbances in the pipe (bad flow profile)
Air bubbles or solids in media
Bad inlet conditions
Troubleshooting/FAQs
59