Modbus
Parameter
Address
Pipe data
40181
300
Number of paths
40149
302
Max sample frequency
40147
303
Sample frequency
40167
304
Rn for path 1
40169
305
Rn for path 2
40171
306
Inner pipe diameter
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
Default
Value
value
range
Product
2
dependent
15
15
0.5
15
Product
3.4E+38
dependent
m
Product
3.4E+38
dependent
m
Product
0.05 ...
dependent
1.200 m
Access
Description
level
R/W
Number of paths on the sensor
Read
The maximum frequency for flow
measurement
HW key
The frequency at which the flow is
measured
Read
R-factor for path 1.
For FUS080/SONOKIT (retrofit)
installations this parameter will
automatically be calculated by the pipe
geometric tool (see 'Pipe geo.
assistant' in 'Device' menu).
Read
R-factor for path 2.
For FUS080/SONOKIT (retrofit)
installations this parameter will
automatically be calculated by the pipe
geometric tool (see 'Pipe geo.
assistant' in 'Device' menu).
Valid only for 2-path solutions
Read
Inner pipe diameter in meters.
For FUS080/SONOKIT (retrofit)
installations this parameter will
automatically be calculated by the pipe
geometric tool (see 'Pipe geo.
assistant' in 'Device' menu).
Parameter lists
A.4 Meter setup
79