Tab. 12.15: Smoke detector sensitivity conditions
12.4

Test/Silence button

Refer to the RADION smoke detector illustration for location of
the Test/Silence button.
Remote monitoring station alarm test
Press the button for fifteen (or 20) seconds to send a fire alarm
signal to the remote monitoring station.
Bosch Security Systems B.V.
Count the number of LED flashes and use the Smoke
detector sensitivity conditions table to determine the status
of the detector's sensitivity and the recommended action.
Testing. Press the Test/Silence button for 4 sec. The
detector performs a Sounder test and a Sensitivity test.
Silence alarm. Press to silence the sounder during an alarm.
After a few minutes, the sounder and alarm resume if
smoke is still present.
Action Recommended
Self-diagnostics failure. Return detector
for service or replacement.
Detector is becoming insensitive. Clean
detector and re-test. If error persists,
replace the detector.
Detector is within normal sensitivity
settings.
Detector is becoming too sensitive.
Confirm that the smoke chamber is
snapped down securely. Clean the sensor
and re-test.
RADION smoke | en
2020.05 | 13 | F.01U.261.834
69