Test/Silence Button; Led; Clean The Detector And Replace The Optical Chamber - Bosch RFRC-OPT Reference Manual

Hide thumbs Also See for RFRC-OPT:
Table of Contents

Advertisement

42
en | RADION smoke
Flashes
2 to 3
4 to 7
8 to 9
Tab. 13.15: Smoke detector sensitivity conditions
13.4
Test/Silence button
Refer to the RADION smoke detector illustration for location of the Test/Silence button.
Remote monitoring station alarm test
Press the button for fifteen (or 20) seconds to send a fire alarm signal to the remote
monitoring station.
Notice!
To avoid a fire department dispatch, contact the remote monitoring station or put the control
panel into the corresponding test mode before performing this test.
13.5

LED

LED
Flashing
ON
OFF
Tab. 13.16: LED
13.6
Clean the detector and replace the optical chamber
Clean the detector cover with a dry or damp cloth as needed to keep it free from dust and
dirt. Clean the detector interior at least yearly.
Cleaning the detector:
1.
2.
3.
2014.12 | 02 | F.01U.261.835
Testing. Press the Test/Silence button for 4 sec. The detector performs a Sounder test
and a Sensitivity test.
Silence alarm. Press to silence the sounder during an alarm. After a few minutes, the
sounder and alarm resume if smoke is still present.
Status
Flashes every 8 sec under normal operation.
Detects smoke, sending an alarm.
Malfunction, replace the batteries, clean the detector, or replace
the optical chamber as required.
Remove the detector from the mounting base.
Remove the batteries.
Slide a slotted screwdriver into the slot on the detector cap and gently push down to pry
off the cap.
Action Recommended
Detector is becoming insensitive. Clean detector and re-test. If
error persists, replace the detector.
Detector is within normal sensitivity settings.
Detector is becoming too sensitive. Confirm that the smoke
chamber is snapped down securely. Clean the sensor and re-
test.
Reference Guide
RADION receiver OP
Bosch Security Systems, Inc.