68
en | RADION smoke
12.1

Battery replacement

Under normal conditions, the LED normally flashes every 8 sec
to indicate normal operating conditions. Replace the battery
when the LED stops flashing, and the sensor chirps every 45
sec.
Silence the low battery trouble chirps for 24 hr by pushing the
Test/Silence button. Refer to the Smoke detector illustration for
locating the Test/Silence button.
12.2

Smoke test

Test smoke detectors annually by using a listed aerosol smoke
tester to simulate an alarm. Follow the instructions on the can.
The LED should remain ON while the detector provides a
continuous tone. The detector automatically resets when smoke
is no longer present. A detector that fails to activate with the
smoke test might require cleaning or replacement.
Notice!
To avoid a fire department dispatch, contact central monitoring
station, or put the system into Test mode before activating the
detector using this method.
12.3

Sensitivity test

Notice!
The control panel recognizes Test Mode as a test. It does not
send an alarm.
The detector includes a Sensitivity Level Test mode for
determining the detector's sensitivity:
1.
2020.05 | 13 | F.01U.261.834
Press and hold the Test/Silence button for 4 sec. The LED
flashes 1 to 9 times.
RADION receiver SD