RADION receiver SD
Flashes
1
2 to 3
4 to 7
8 to 9
Table 9.2: Smoke detector sensitivity conditions
9.4

Test/Silence button

Refer to the RADION smoke detector illustration for location of the Test/Silence button.
9.5

LED

LED
Flashing
ON
OFF
Table 9.3: LED
9.6

Clean the detector and replace the optical chamber

Clean the detector cover with a dry or damp cloth as needed to keep it free from dust and
dirt. Clean the detector interior at least yearly.
Cleaning the detector:
1.
2.
3.
Figure 9.2: Remove the detector cap
4.
Bosch Security Systems, Inc.
Testing. Press the Test/Silence button for 4 sec. The detector performs a Sounder test
and a Sensitivity test.
Silence alarm. Press to silence the sounder during an alarm. After a few minutes, the
sounder and alarm resume if smoke is still present.
Status
Flashes every 8 sec under normal operation.
Detects smoke, sending an alarm.
Malfunction, replace the batteries, clean the detector, or replace
the optical chamber as required.
Remove the detector from the mounting base.
Remove the batteries.
Slide a slotted screwdriver into the slot on the detector cap and gently push down to pry
off the cap.
Squeeze the optical chamber where indicated and pull it up and away from the detector.
Action Recommended
Self-diagnostics failure. Return detector for service or
replacement.
Detector is becoming insensitive. Clean detector and re-test. If
error persists, replace the detector.
Detector is within normal sensitivity settings.
Detector is becoming too sensitive. Confirm that the smoke
chamber is snapped down securely. Clean the sensor and re-
test.
Reference Guide
RADION smoke | en
41
2014.03 | 06 | F.01U.261.834