Measuring using module parameters
This section describes the method to calculate the communication success rate.
1.
Setting of module parameters
[007ER-1V680D1] or [007ER-1V680D2]  [Module Parameter]  [Basic Setting]
Set "TEST mode (Communication success rate)" to "Operation mode".
Check that "Enable" is set to "Enable channel 1 TEST mode" and "Enable channel 2 TEST mode (ER-1V680D2 use)".
2.
Writing data to the CPU module
To switch to TEST mode, write the data to the CPU module and reset the CPU module or power off and on.
3.
Check of test results
The test results are stored in Processing result monitor storage area (Un\G42, Un\G4042). ( Page 82 Test results)
Test results
Processing result monitor storage area
CH1
Un\G42
The test results can be checked with the operation indication lamps of amplifier. For details, refer to the
manuals for the amplifier to use.
6 FUNCTIONS
82
6.4 Test Function
Data format
CH2
Un\G4042
■When completed successfully (C1 + measurement result)
C101 to C199 [BCD] (Unit: %)
C1EE: 0% (measurement result)
C1FF: 100% (measurement result)
■When completed with an error (E0 + error code)
E07CH: Antenna error