Mitsubishi Electric ER-1V680D1 User Manual page 131

Rfid interface module, melsec iq-r series recognized
Table of Contents

Advertisement

■No. of processing points specification area (Un\G4, Un\G4004)
This area is used to specify the number of processed bytes of RF tag to be subject to reading or writing.
When "With ASCII/HEX conversion" is set to "Read/Write data code setting", specify an even number to the number of bytes
of ASCII to read/write from/to the RF tag. When an odd number is specified, the status flag (b0) in Error details storage area
(Un\G41, Un\G4041) and Error detection (X5, XD) turn on.
The system operates with the setting of ID command execution request (Y14, Y1C) when starting up.
■Command option specification area (Un\G5, Un\G4005)
This area is used to specify the details of the command processing method when the Write calculation, Control number of
writes, and Copy commands are executed. The system operates with the setting of ID command execution request (Y14,
Y1C) when starting up.
Command
Write calculation
Manage number of writes
Copy
■Auto command wait time setting area (Un\G10, Un\G4010)
This area is used to set the wait time in BCD for the RF tag response after ID command execution request (Y14, Y1C) is
turned on with an auto command (Auto, Auto Repeat, FIFO Repeat, Multi-repeat). The system operates with the setting of ID
command execution request (Y14, Y1C) when starting up.
Setting value
0000, value other than BCD
0001 to 9999
Ex.
When setting 3 seconds to the wait time, set 0030H.
■Processing result monitor switch setting area (Un\G11, Un\G4011)
This area is used to set the data to store in Processing result monitor storage area (Un\G42, Un\G4042). The system operates
with the setting of ID command execution request (Y14, Y1C) when starting up.
Setting value
0001
Other than 0001
Processing result
■Module status storage area (Un\G40, Un\G4040)
The operation status of RFID interface module is stored.
Bit
Name
*1
0
Antenna error
1
24VDC power supply error
2
TEST mode
3 to 15
System area
*1 When 24VDC power supply is not normally supplied, the antenna error (b0) is changed to 0 or 1.
Description
The addition data or subtraction data is stored.
The addition data or subtraction data is stored.
The copy destination address is specified.
Description
The ID command is continually executed until the response from the RF tag.
When an RF tag is not detected within the set value [BCD]  0.1 seconds, the ID command stops due to Tag not present
error and Error detection (X5, XD) turns on.
Description
The noise level is stored in Processing result monitor storage area (Un\G42, Un\G4042).
The communication time is stored in Processing result monitor storage area (Un\G42, Un\G4042).
Description
0: Normal operation, or antenna is not connected.
1: Unavailable antenna is connected.
0: 24VDC power supply is normally supplied.
1: 24VDC power supply is not normally supplied.
0: RUN mode
1: TEST mode
0: Fixed
Reference
Page 52 Write calculation
Page 62 Manage number of
writes
Page 56 Copy
APPX
Appendix 3 Buffer Memory
A
129

Advertisement

Table of Contents
loading

This manual is also suitable for:

Er-1v680d2

Table of Contents