Setting Guidelines - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
Data
IEC09000758 V3 EN-US
Figure 381: Redundant station bus
19.2.6.3

Setting guidelines

Redundant communication (PRP) is configured in the local HMI under Main menu/
Configuration/Communication/Ethernet configuration/PRP
The settings are found in the Parameter Setting tool in PCM600 under IED Configuration/
Communication/Ethernet configuration/PRP. By default the settings are read only in the
Parameter Settings tool, but can be unlocked by right clicking the parameter and selecting
Lock/Unlock Parameter.
Operation : The redundant communication will be activated when this parameter is set to
On. After confirmation the IED will restart and the setting alternatives Rear OEM - Port AB and
CD will not be further displayed in the local HMI. The ETHLANAB and ETHLANCD in the
Parameter Setting Tool are irrelevant when the redundant communication is activated, only
PRP IPAdress and IPMask are valid.
Application manual
Station Control System
Duo
Data
Switch A
1 2
AB
CD
OEM
Configuration
PRP
=IEC09000758=3=en=Original.vsd
Redundancy
Supervision
Data
Switch B
1 2
Data
IED
PRPSTATUS
Section 19
Station communication
GUID-6AD04F29-9B52-40E7-AA07-6D248EF99FC6 v2