Setting Of Reverse Zone - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
Larger overreach than the mentioned 80% can often be acceptable due to fault current infeed
from other lines. This requires however analysis by means of fault calculations.
If any of the above gives a zone 2 reach less than 120%, the time delay of zone 2 must be
increased by approximately 200ms to avoid unwanted operation in cases when the
telecommunication for the short adjacent line at remote end is down during faults. The zone 2
must not be reduced below 120% of the protected line section. The whole line must be covered
under all conditions.
The requirement that the zone 2 shall not reach more than 80% of the shortest adjacent line at
remote end is highlighted in the example below.
If a fault occurs at point F see figure 171, the IED at point A senses the impedance:
V
Z
=
AF
I
EQUATION302 V5 EN-US
IEC09000256 V2 EN-US
Figure 171: Setting of overreaching zone
7.12.3.4

Setting of reverse zone

The reverse zone is applicable for purposes of scheme communication logic, current reversal
logic, weak-end infeed logic, and so on. The same applies to the back-up protection of the bus
bar or power transformers. It is necessary to secure, that it always covers the overreaching
zone, used at the remote line IED for the telecommunication purposes.
Consider the possible enlarging factor that might exist due to fault infeed from adjacent lines.
Equation
blocking scheme, weak-end infeed, and so on.
³
Zrev
EQUATION1525 V5 EN-US
Where:
ZL
Z2rem
In many applications it might be necessary to consider the enlarging factor due to fault
current infeed from adjacent lines in the reverse direction in order to obtain certain sensitivity.
Application manual
I
+
I
I
A
A
C
=
Z
+
Z
+
AC
CF
I
A
A
Z
AC
A
I
A
Z<
292
can be used to calculate the reach in reverse direction when the zone is used for
(
)
×
-
1.2
ZL
Z rem
2
is the protected line impedance
is zone 2 setting at remote end of protected line.
+
I
+
I
A
C
B
R
=
Z
+
1
AC
F
I
A
Z
CB
F
C
Z
CF
I
+ I
A
C
I
C
I
I
+
I
C
C
B
+
 ⋅
Z
+
1
+
 ⋅
C
F F
I
I
A
A
I
B
B
IEC09000256-2-en.vsd
GUID-B633CF2C-28B2-4FDD-BE0E-D09CA434F01F v1
Section 7
Impedance protection
R
F
(Equation 291)
(Equation 292)
297

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret670

Table of Contents