ABB RELION 670 Series Applications Manual page 568

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 14
Control
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO), and each bus-
coupler bay (ABC_BC) are needed:
Signal
QB1OPTR
QB2OPTR
QB220OTR
QB7OPTR
VPQB1TR
VPQB2TR
VQB220TR
VPQB7TR
EXDU_BB
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module (A1A2_DC)
is used for different busbars, that is, for both bus-section disconnectors A1A2_DC and
B1B2_DC.
Signal
DCOPTR
VPDCTR
EXDU_DC
If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and EXDU_DC are set to 1
(TRUE).
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section
coupler bay (A1A2_BS) rather than the bus-section disconnector bay (A1A2_DC) must be used.
For B1B2_BS, corresponding signals from busbar B are used. The same type of module
(A1A2_BS) is used for different busbars, that is, for both bus-section circuit breakers A1A2_BS
and B1B2_BS.
Signal
QB1OPTR
QB2OPTR
VPQB1TR
VPQB2TR
EXDU_BS
For a busbar earthing switch, these conditions from the A1 busbar section are valid:
562
QB1 is open.
QB2 is open (AB_TRAFO, ABC_LINE)
QB2 and QB20 are open (ABC_BC)
QB7 is open.
The switch status of QB1 is valid.
The switch status of QB2 is valid.
The switch status of QB2and QB20 is valid.
The switch status of QB7 is valid.
No transmission error from the bay that contains the above information.
The bus-section disconnector is open.
The switch status of bus-section disconnector DC is valid.
No transmission error from the bay that contains the above information.
QB1 is open.
QB2 is open.
The switch status of QB1 is valid.
The switch status of QB2 is valid.
No transmission error from the bay BS (bus-section coupler bay) that contains
the above information.
1MRK 504 152-UEN B
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret670

Table of Contents