Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
In some applications, for instance cable lines, the angle of the loop might be less than 60°. In
these applications, the settings of fault resistance coverage in forward and reverse direction,
RFFwPE and RFRvPE for phase-to-earth faults and RFFwPP and RFRvPP for phase-to-phase
faults have to be increased to avoid that FDPSPDIS characteristic shall cut off some part of the
zone characteristic. The necessary increased setting of the fault resistance coverage can be
derived from trigonometric evaluation of the basic characteristic for respectively fault type.
Phase-to-earth fault in forward direction
With reference to figure 157, the following equations for the setting calculations can be
obtained.
Application manual
Index PHS in images and equations reference settings for Phase selection with
load encroachment function FDPSPDIS and index Zm reference settings for
Distance protection function (ZMQPDIS).
Section 7
Impedance protection
M13142-6 v7
277