ABB RELION 670 Series Applications Manual page 447

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
Set value
L1
L2
L3
The function has two stages that can be set independently.
With the parameter
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is smaller than the set pick up power value Power1(2)
IEC06000441 V1 EN-US
Figure 267: Underpower mode
The setting
setting is given in p.u. of the generator rated power, see equation 472.
Minimum recommended setting is 0.2% of S
used.
=
S
N
EQUATION1708 V1 EN-US
Application manual
Mode
OpMode1(2) the function can be set On / Off .
Q
Power1(2)
Operate
Power1(2) gives the power component pick up value in the Angle1(2) direction. The
×
×
3
UBase IBase
Formula used for complex power calculation
*
= ×
×
S
3
U
I
L
1
L
1
EQUATION1703 V1 EN-US
*
= ×
×
S
3
U
I
L
2
L
2
EQUATION1704 V1 EN-US
*
= ×
×
S
3
U
I
L
3
L
3
EQUATION1705 V1 EN-US
Angle1(2)
en06000441.vsd
when metering class CT inputs into the IED are
N
Current protection
(Equation 469)
(Equation 470)
(Equation 471)
P
(Equation 472)
Section 8
441