Identification; Application; Setting Guidelines; Automationbits, Command Function For Dnp3.0 Autobits - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 14
Control
14.8.1

Identification

Function description
Single point generic control 8 signals
14.8.2

Application

The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands, designed to bring in commands from REMOTE (SCADA) to those parts of the
logic configuration that do not need complicated function blocks that have the capability to
receive commands (for example SCSWI). In this way, simple commands can be sent directly to
the IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGGIO function blocks.
14.8.3

Setting guidelines

The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via
the local HMI or PCM600.
Operation : turning the function operation On / Off .
There are two settings for every command output (totally 8):
Latchedx : decides if the command signal for output x is Latched (steady) or Pulsed .
tPulsex : if Latchedx is set to Pulsed , then tPulsex will set the length of the pulse (in seconds).
14.9
AutomationBits, command function for DNP3.0
AUTOBITS
14.9.1

Identification

Function description
AutomationBits, command function
14.9.2

Application

Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in order to
get into the configuration the commands coming through the DNP3.0 protocol.The AUTOBITS
function plays the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV
608
IEC 61850
identification
SPC8GAPC
PSTO is the universal operator place selector for all control functions. Even if
PSTO can be configured to allow LOCAL or ALL operator positions, the only
functional position usable with the SPC8GAPC function block is REMOTE.
IEC 61850
identification
for DNP3
IEC 60617
identification
-
IEC 60617
identification
AUTOBITS
-
1MRK 504 152-UEN B
SEMOD176456-2 v3
ANSI/IEEE C37.2
device number
-
SEMOD176511-4 v4
SEMOD176518-4 v5
SEMOD158589-1 v3
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
ANSI/IEEE C37.2
device number
-
SEMOD158637-5 v4
Application manual