Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
( )
>
U
%
IECEQUATION2290 V1 EN-US
The setting is dependent of the required sensitivity of the protection and the system earthing.
In non-effectively earthed systems the residual voltage can be maximum the rated phase-to-
earth voltage, which should correspond to 100%.
In effectively earthed systems this value is dependent of the ratio Z0/Z1. The required setting
to detect high resistive earth-faults must be based on network calculations.
tn : time delay of step n , given in s. The setting is highly dependent of the protection
application. In many applications, the protection function has the task to prevent damages to
the protected object. The speed might be important for example in case of protection of
transformer that might be overexcited. The time delay must be co-ordinated with other
automated actions in the system.
tResetn : Reset time for step n if definite time delay is used, given in s. The default value is 25
ms.
tnMin : Minimum operation time for inverse time characteristic for step n , given in s. For very
high voltages the overvoltage function, using inverse time characteristic, can give very short
operation time. This might lead to unselective trip. By setting
time for other protections such unselective tripping can be avoided.
ResetTypeCrvn : Set reset type curve for step n . This parameter can be set:
Instantaneous , Frozen time , Linearly decreased . The default setting is Instantaneous .
tIResetn : Reset time for step n if inverse time delay is used, given in s. The default value is 25
ms.
kn : Time multiplier for inverse time characteristic. This parameter is used for co-ordination
between different inverse time delayed undervoltage protections.
ACrvn , BCrvn , CCrvn , DCrvn , PCrvn : Parameters for step n , to set to create programmable
undervoltage inverse time characteristic. Description of this can be found in the technical
reference manual.
CrvSatn : Set tuning parameter for step n . When the denominator in the expression of the
programmable curve is equal to zero the time delay will be infinity. There will be an undesired
discontinuity. Therefore, a tuning parameter
phenomenon. In the voltage interval
U> · (1.0 + CrvSatn /100). If the programmable curve is used this parameter must be calculated
so that:
CrvSatn
×
B
100
EQUATION1448 V1 EN-US
HystAbsn: Absolute hysteresis for step n , set in % of UBase . The setting of this parameter is
highly dependent of the application.
Application manual
(
)
×
UBase kV
3
-
>
C
0
CrvSatn is set to compensate for this
U> up to U> · (1.0 + CrvSatn /100) the used voltage will be:
Voltage protection
(Equation 496)
t1Min longer than the operation
(Equation 497)
Section 9
475