Identification; Application; Setting Guidelines; Running Hour-Meter Teilgapc - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
17.8.1

Identification

Function description
Limit counter
17.8.2

Application

Limit counter (L4UFCNT) is intended for applications where positive and/or negative flanks on
a binary signal need to be counted.
The limit counter provides four independent limits to be checked against the accumulated
counted value. The four limit reach indication outputs can be utilized to initiate proceeding
actions. The output indicators remain high until the reset of the function.
It is also possible to initiate the counter from a non-zero value by resetting the function to the
wanted initial value provided as a setting.
If applicable, the counter can be set to stop or rollover to zero and continue counting after
reaching the maximum count value. The steady overflow output flag indicates the next count
after reaching the maximum count value. It is also possible to set the counter to rollover and
indicate the overflow as a pulse, which lasts up to the first count after rolling over to zero. In
this case, periodic pulses will be generated at multiple overflow of the function.
17.8.3

Setting guidelines

The parameters for Limit counter L4UFCNT are set via the local HMI or PCM600.
17.9

Running hour-meter TEILGAPC

17.9.1
Identification
Function Description
Running hour-meter
17.9.2
Application
The function is used for user-defined logics and it can also be used for different purposes
internally in the IED. An application example is to accumulate the total running/energized time
of the generator, transformer, reactor, capacitor bank or even line.
Settable time limits for warning and alarm are provided. The time limit for overflow indication
is fixed to 99999.9 hours. At overflow the accumulated time resets and the accumulation
starts from zero again.
17.9.3
Setting guidelines
The settings
resolution of the settings is 0.1 hours (6 minutes).
Application manual
IEC 61850
identification
L4UFCNT
IEC 61850
identification
TEILGAPC
tAlarm and tWarning are user settable limits defined in hours. The achievable
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
IEC 60617
ANSI/IEEE C37.2 device
identification
number
-
-
Section 17
Monitoring
GUID-F3FB7B33-B189-4819-A1F0-8AC7762E9B7E v2
GUID-41B13135-5069-4A5A-86CE-B7DBE9CFEF38 v2
GUID-5AECCDBC-7385-4D9F-940C-9D4A0E59B106 v1
GUID-DA5DA8D7-4821-4BFB-86CC-28658E376270 v1
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
GUID-225D8341-2D31-49F1-9B49-571346C0FE26 v1
GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1
659

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret670

Table of Contents