Section 14
Control
IEC13000016 V2 EN-US
Figure 297: APC - Local remote function block
14.2.1.2

Switch controller (SCSWI)

SCSWI may handle and operate on one three-phase device or three one-phase switching
devices.
After the selection of an apparatus and before the execution, the switch controller performs
the following checks and actions:
A request initiates to reserve other bays to prevent simultaneous operation.
Actual position inputs for interlocking information are read and evaluated if the operation
is permitted.
The synchrocheck/synchronizing conditions are read and checked, and performs
operation upon positive response.
The blocking conditions are evaluated
The position indications are evaluated according to given command and its requested
direction (open or closed).
The command sequence is supervised regarding the time between:
Select and execute.
Select and until the reservation is granted.
Execute and the final end position of the apparatus.
Execute and valid close conditions from the synchrocheck.
At error the command sequence is cancelled.
532
1MRK 504 152-UEN B
IEC13000016-2-en.vsd
M16596-3 v4
Application manual